CVE-2018-5459 | BDVDB-2026-96424 Detail
WAGO PFC200 Series
Description#
An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455.
Impact#
No impact statement in the source data.
Weaknesses#
- CWE-287 Improper Authentication
References#
Exploit#
No public exploit known
History#
- Version 1Record published in the CVE List.
- Version 2Most recent update recorded in the CVE List.