CVE-2026-11826 | BDVDB-2026-349361 Detail
openplcprojectOpenPLC_v3
Description#
OpenPLC_v3 contains a heap-based buffer overflow in the getData() function in webserver/core/modbus_master.cpp. getData() reads characters between two delimiters into a caller-supplied buffer with no size parameter and no bounds check. In parseConfig() the function is invoked with the 100-byte heap-allocated MB_device.dev_name field. An authenticated attacker with access to the OpenPLC web interface can send a crafted HTTP POST to the /modbus endpoint with an oversized device_name value; the value is persisted to mbconfig.cfg and parsed on load, overflowing dev_name and overwriting adjacent struct fields (protocol at offset 108, dev_address at offset 109, ip_port at offset 210). A 200-byte payload writes 100 bytes past the allocation. The result is heap corruption leading to runtime crash and denial of service of the PLC process control loop, with attacker-controlled overwrite of adjacent configuration fields. The upstream repository was archived on 2026-04-04 and no fix is expected; the vendor has confirmed the issue does not affect OpenPLC Runtime v4.
Impact#
Per CVSS v3.1: confidentiality impact high, integrity impact high, availability impact high. Attack vector: network.
Weaknesses#
- CWE-122 Heap-based Buffer Overflow
References#
- https://gist.github.com/Shukhrat-03/5cf1825b72e485ef98a32958dfbc611a#security-vulnerability-report
- https://github.com/thiagoralves/OpenPLC_v3/commit/b4702061dc14d1024856f71b4543298d77007b88
- https://github.com/thiagoralves/OpenPLC_v3
- https://www.vulncheck.com/advisories/openplc-v3-heap-based-buffer-overflow-in-modbus-master-getdata
Exploit#
No public exploit known
History#
- Version 1Record published in the CVE List.
- Version 2Most recent update recorded in the CVE List.