CVE-2026-3611 | BDVDB-2026-320146 Detail
HoneywellIQ4E
Description#
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Impact#
Per CVSS v3.1: confidentiality impact high, integrity impact high, availability impact high. Attack vector: network.
Weaknesses#
- CWE-306 Missing Authentication for Critical Function
References#
Exploit#
No public exploit known
History#
- Version 1Record published in the CVE List.
- Version 2Most recent update recorded in the CVE List.