CVE-2026-1773 | BDVDB-2026-317008 Detail
Hitachi EnergyRTU500 series CMU firmware
Description#
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.
Impact#
CAPEC-278 Web Services Protocol Manipulation
Weaknesses#
- CWE-184 Incomplete List of Disallowed Inputs
References#
Exploit#
No public exploit known
History#
- Version 1Record published in the CVE List.