CVE-2021-27391 | BDVDB-2026-160839 Detail
SiemensAPOGEE MBC (PPC) (P2 Ethernet)
Description#
A vulnerability has been identified in APOGEE MBC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE MEC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE PXC Compact (BACnet) (All versions < V3.5.3), APOGEE PXC Compact (P2 Ethernet) (All versions >= V2.8), APOGEE PXC Modular (BACnet) (All versions < V3.5.3), APOGEE PXC Modular (P2 Ethernet) (All versions >= V2.8), TALON TC Compact (BACnet) (All versions < V3.5.3), TALON TC Modular (BACnet) (All versions < V3.5.3). The web server of affected devices lacks proper bounds checking when parsing the Host parameter in HTTP requests, which could lead to a buffer overflow. An unauthenticated remote attacker could exploit this vulnerability to execute arbitrary code on the device with root privileges.
Impact#
Per CVSS v3.1: confidentiality impact high, integrity impact high, availability impact high. Attack vector: network.
Weaknesses#
- CWE-120 Buffer Copy without Checking Size of Input ('Classic Buffer Overflow')
References#
Exploit#
No public exploit known
History#
- Version 1Record published in the CVE List.
- Version 2Most recent update recorded in the CVE List.