SiemensSIMATIC S7-300 CPUs

Description#

A vulnerability has been identified in SIMATIC S7-300 CPUs (All versions < V3.X.16). The affected CPUs improperly validate S7 communication packets which could cause a Denial-of-Service condition of the CPU. The CPU will remain in DEFECT mode until manual restart. Successful exploitation requires an attacker to be able to send a specially crafted S7 communication packet to a communication interface of the CPU. This includes Ethernet, PROFIBUS, and Multi Point Interfaces (MPI). No user interaction or privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the core functionality of the CPU, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.

Impact#

Per CVSS v3.1: confidentiality impact none, integrity impact none, availability impact high. Attack vector: network.

Weaknesses#

  • CWE-20 Improper Input Validation

References#

Exploit#

No public exploit known

History#

  1. Version 1Record published in the CVE List.
  2. Version 2Most recent update recorded in the CVE List.